Diagram of irrigation intensity dependence on pressure at application of water solutions with capacity factor K = 0.6 on 12 m2 protected area.

Diagram of irrigation intensity dependence on pressure at application of foam solutions with capacity factor K = 0.6 on 12 m2 protected area.

Sprinkler map of irrigation intensity for upright sprinklers at application of water and water solutions with capacity factor K=0,6/115/8,0
(0,1 and 0,2 MPa) and (0,3 and0,4 MPa)
Installation height – 2.5 m.

Sprinkler map of irrigation intensity for upright sprinklers at application of foam solutions with capacity factor K= 0,6/115/8,0
(0,1 and 0,2 MPa) and (0,3 and0,4 MPa)
Installation height – 2.5 m.

| Atomizer weight | 0,07 kg |
| Connecting thread | ½ inch |
| Dimensions | 58х30 mm |
| Installation orientation | Upright |
| K-factor | 8,0 (115) |
| Outlet diameter | 13 mm |
| Performance factor | 0,6 |
| Protected area | 12 m2 |
| Sprinkler flask diameter | 3 mm |
| Sprinkler response temperature | 57° С, 68° С , 93°С |