Diagram of irrigation intensity dependence on pressure at application of water solutions with capacity factor K = 0.42 on 12m2 protected area

Diagram of irrigation intensity dependence on pressure at application of foam solutions with capacity factor K = 0.42 on 12m2 protected area

Diagram of irrigation intensity dependence on pressure at application of water and water solutions with capacity factor K=0.42 on 12 m2 (two or more)
Installation height 2,5m for upright water-mist sprinklers

Sprinkler map of irrigation intensity for upright sprinklers at application of water and water solutions with capacity factor K=0,42/80/5,6
(0,1; 0.2; 0,3 and 0,4 MPa)
Installation height – 2.5 m.

Sprinkler map of irrigation intensity for upright sprinklers at application of foam solutions with capacity factor K=0,42/80/5,6
(0,15; 0.2; 0,3 and 0,4 MPa)
Installation height – 2.5 m.

| Atomizer weight | 0,072 kg |
| Connecting thread | ½ inch |
| Dimensions | 58х30 mm |
| Installation orientation | Pendent |
| K-factor | 5,5 (80) |
| Outlet diameter | 11,8 mm |
| Performance factor | 0,42 |
| Protected area | 12 m2 |
| Sprinkler flask diameter | 3 mm |
| Sprinkler response temperature | 57° С, 68° С , 93°С |